Electrical measuring instruments >> transformers industrial >> current transformers >> 10kV voltage class

TOL-10-М-2

For order is possible effectively delivery of any quantity.
Current transformer TOL-10-M-2 (TOL10M2, TOL 10 M 2, TOL10-M-2, TOL10 M 2, TOL10M-2, TOL10M 2)
 
Technical characteristics of the instrument current transformers TOL-10-M-2:
 
The number of secondary windings - 2;
Nominal AC frequency - 50 Hz;
Rated voltage - 10kV;
Maximum operating voltage - 12kV;
Rated secondary current of the current transformer unit TOL-10-M-2 - 5A;
Rated primary current - 2500A, 3000A, 4000A;
Accuracy class of the instrument current transformer TOL-10-M-2:
- Secondary winding for measurement - 0,5; 0,5 S, 0,2; 0,2 S;
- Secondary protection - 10P (5P);
Rated secondary current transformer load device TOL-10-M-2:
- Secondary winding for measurement:
- At cosφ = 1 - 1 B · A · 2B A, 2.5 V · A;
- At cosφ = 0,8 - 3V · A · A 5V, 10V · A * · A 15 V, 20 V · A · A 25V, 30V · A;
- Secondary to protect:
- At cosφ = 0,8 - 3V · A · A 5V, 10V · A · A * 15V, 20V · A · A 25V, 30V · A;
Rated current ratio of secondary winding for protection (at rated secondary load 15V · A) - at least 10;
Nominal factor of safety devices in the winding for measurement accuracy class 0,5, 0,2, 0,5 S (at rated secondary load 10V · A) instrument current transformer TOL-10-M-2 - no more than 13;
Nominal factor of safety devices in the winding for measurement accuracy class 0,2 S (at rated secondary load 10V · A) - not more than 10;
A one-second thermal current instrument transformer current TOL-10-M-2 - 64kA;
Current withstand - 152.5 kA
Note. * - The default value, and the value of secondary loads, secondary current limit multiplicity of secondary winding for protection, a safety factor of secondary devices for measurement, the instrument accuracy classes CT TOL-10-M-2 are specified in the order; transformers can be manufactured with an inverted position primary findings; Example for transformer with an inverted arrangement of the primary conclusions - TOL-10-M-2I;
Calculated values ​​of the nominal current ratio secondary instrument current transformer TOL-10-M-2 for the defense in terms of rated secondary load in accuracy classes 5P and 10P are given in Table 1;
 
Table 1 Calculated values ​​of the nominal current ratio secondary instrument current transformer TOL-10-M-2 for the defense in terms of rated secondary load in accuracy classes 5P and 10P;
 
Rated secondary burden, VA
3
5
10
15
20
30
40
50
Ratio of transformation
Rated current ratio
2500/5
18
13
11
10
9
7
6
5
3000/5
19
 
General view of the instrument current transformer TOL-10-M-2 is shown in Figure 1;
 
Figure 1: General view of the instrument current transformer TOL-10-M-2
 
TOL-10-M-2 - Current transformer - Drawing.
 
Weight of the device current transformer TOL-10-M-2 - 28kg;
The transformers are manufactured in climatic design "T" and "NF" and are intended for indoor use in:
Height above the sea level - no more than 1000 m.
- Ambient temperature with the heat the air inside the switchgear - from -45 ° C to +50 ° C for the performance of "U2" and from -10 ° C to +55 ° C for the performance of "T2";
- Environment explosive, without dust, reactive gases and vapors in concentrations destroy metal and insulation;
- Working position - any;
In current transformers may be used to account for the secondary windings, Class 0,2 S and 0,5 S with the value of the secondary load below 25% of nominal;
The minimum weight for the device current transformer windings TOL-10-M-2 accuracy classes 0,2 S and 0,5 S is 1B · A;
The certificate on the current transformers with secondary windings for accounting accuracy classes 0,2 S and 0,5 S indicates the measured current and the angular error at rated secondary burden 1B · A;
Can manufacture transformers with different transformation ratios of secondary windings;
The manufacturer guarantees that the quality of the instrument current transformer TOL-10-M-2 technical requirements specifications provided the customer terms and conditions of storage, transportation, installation, operation, and its specified operational documentation.

Photos: TOL-10-М-2

TOL-10-М-2 transformer image.
TOL-10-М-2 transformer image.
TOL-10-М-2 transformer scheme.
TOL-10-М-2 transformer scheme.