Radiometric devices >> combustible Gas Detector

Leak detector 202Eh

available:
12 pieces
For order is possible effectively delivery of any quantity.
202Eh leak detector (202-Ex, 202 Ex)
 
202Eh leak detector is used in hazardous areas, and outdoors in areas where there is produced, stored and used gas, such as chemical, petrochemical, metallurgical, pharmaceutical industry, LPG ​​(liquefied petroleum gas) station to detect and show the gas leak.
This device can be installed on two levels of alarm values. The detector can signal when the gas concentration reaches a given.
 
Technical characteristics of the devices 202Eh leak detectors:
 
The relative sensitivity of the instrument to leak detector combustible gas 202Eh:
 
Type of gas
Explosive concentrations of LEL (% V / V)
The relative sensitivity of the% LEL
Methane
5.00
100
Methanol
6.70
70
Hydrogen
4.00
80
Ethane
1.20
30
Ethanol
3.30
40
Ethylene
2.70
50 ~ 70
Ethylene
2.20
30
Propane
2.10
55
2-butanone
1.90
20
Acetone
2.60
35
Bhutan
1.80
50
Heptane
1.05
35
Octane
0.95
30
Pentane
1.40
40
Cyclohexane
1.30
40
Gazoline
1.40
40
Isopropanol
2.20
35
Toluene
1.20
35
Acetylene
2.70
50-60%
 
The table shows the relative sensitivity of the combustible gas to methane;
Leak Detection - on the principle of catalytic combustion;
Detection of leak detection device 202Eh gas - fuel gas;
Measuring range - 0% -100% (NUV - low level of protection - at the lower concentration of flammable gas to create an explosion in the air at a meeting with an open fire);
Resolution of the display device 202Eh leak detector - 0.1%;
Accuracy - ± 2%;
Response time - <30 sec;
Operating temperature leak detector device 202Eh - from -10 ℃ to +60 ℃;
Operating Humidity - <99%;
 
202Eh - Leak detector - The arrangement of buttons and elements on the front panel. 
 
Figure 1 shows the arrangement of buttons and elements on the front panel 202Eh leak detector:
1 - Button CLR;
2 - Button MODE;
3 - Button MEM;
4 - Button ZERO;
5 - Speaker;
6 - Display;
7 - side button;
8 - the probe;
Figure 2 shows the elements of the display device 202Eh leak detector:
1 - a map of recorded numerical values;
2 - an indicator of stored data;
3 - Indicator data - measuring mode;
4 - an indicator measuring mode;
5 - an indicator of the zero calibration;
6 - an indicator of a warning signal;
7 - LED warning signal 2;
8 - battery indicator;
9 - shows the measured values,;
The device is able to leak detector 202Eh zero calibration, for which they should be placed in clean air (no fuel gas) for 1 minute in the measurement mode;
Display Mode - digital display with large screen LCD;
The method of signaling - acousto-optic;
Power supply leak detector 202Eh - 4x1, 5V AA batteries;
Current consumption:
- In the mode of measurement of the state - <110mA;
- No measurement of the state - <15mA;
The manufacturer guarantees the quality of leak detection device 202Eh technical requirements specifications, subject to the consumer the terms and conditions of storage, transportation, installation, operation, established specifications and operational documentation.

Photos Leak detector 202Eh

Leak detector 202Ех device image.
Leak detector 202Ех device image.