TSHP-0,66-I

For order is possible effectively delivery of any quantity.
Current transformer TSHP-0,66-I (TSHP-0,66-1, TSHP0,66I, TSHP 0,66 I, TSHP0,66-I, TSHP0,66 I, TSHP-0,66I, TSHP 0,66I)
 
Current transformer TSHP-0,66-I intended to send a signal measurement information instrumentation installations in AC 50Hz or 60Hz with rated voltage up to 0.66 kV.
 
Technical characteristics of the instrument current transformers TSHP-0,66-I:
 
Accuracy class - 0,5; 0,5 S, 0,2; 0,2 S, 1, 3, 5;
Number of windings - 1;
Rated current of the current transformer unit TSHP-0,66-I - 75A-600A;
Rated secondary current - 1A, 5A;
Rated primary current, rated secondary burden and accuracy class of the instrument current transformer TSHP-0,66-I are given in Table 1;
 
Table 1 Rated primary current, rated secondary burden and accuracy class of the instrument current transformer TSHP-0,66-I
 
Rated primary current
Rated secondary burden secondary at cosφ
Accuracy class
0.8 (inductive load-active)
1
75A, 80A
· A 3V, 5V · A
-
3.5.
100A
5 V · A
0.5, 3
3B · A
0,5 S, 0,5, 1
150A, 200A
· A 3V, 5V · A
0,5 S, 0,5, 1
10 V · A
3
300A, 400A, 500A, 600A
3 B · A · A 5V, 10V · A
0,2 S, 0,5 S, 0,5
300A, 400A
15 V · A
0.5, 1
500A
· A 15V, 20V · A
0.5
600A
15 V · A
0,5 S, 0,5
· A 20V, 30V · A
0.5
75A, 80A
-
1B · A
0,5 S, 0,5
2B · A, 2.5 V · A
0.5, 1
100A, 150A, 200A
· A 1B, 2B · A, 2.5 V · A
0,5 S, 0,5
300A, 400A, 500A, 600A
0,2 S, 0,5 S, 0,5
 
Rated primary current and the highest primary current working device CT TSHP-0,66-I are given in Table 2;
 
Table 2 Primary rated current and the largest primary current working device CT TSHP-0,66-I
 
Parameter's name
Parameter value
Rated primary current
1A
5A
10A
15A
20A
30A
40A
50A
Maximum operating current of primary
1A
5A
10A
16A
20A
32A
40A
50A
Rated primary current
75A
80A
100A
150A
200A
300A
400A
500A
Maximum operating current of primary
80A
80A
100A
160A
200A
320A
400A
500A
Rated primary current
600A
750A
800A
1000A
1200A
1500A
2000A
 
Maximum operating current of primary
630A
800A
800A
1000A
1250A
1600A
2000A
 
 
The coefficients of safety devices CT TSHP-0,66-I according to the rated primary current, rated secondary burden and accuracy class are shown in Table 3;
 
Table 3 The coefficients security appliance CT TSHP-0,66-I according to the rated primary current, rated secondary burden and accuracy class
 
Rated primary current
Rated secondary current
Accuracy class
Rated safety factor at rated secondary burden
 
1B · A
2B · A
2,5 V · A
3B · A
5 V · A
10 V · A
15 V · A
20 V · A
30 V · A
300A
1A
0,2 S
8
5
5
5
5
-
-
-
-
400A
8
-
-
-
-
3
-
-
-
500A
7
5
5
5
4
3
-
-
-
600A
7
5
5
5
5
3
3
-
-
75A, 80A
0,5 S
5
-
-
-
-
-
-
-
-
100A
5
5
5
5
5
-
-
-
-
150A
10
5
5
5
5
-
-
-
-
200A
5
5
5
5
5
-
-
-
-
300A
8
5
5
5
5
3
-
-
-
400A
13
10
10
10
10
-
-
-
-
500A
14
12
10
10
10
-
-
-
-
600A
14
12
12
10
10
7
5
-
-
75A, 80A
0.5
5
5
5
-
-
-
-
-
-
100A
5
5
5
5
5
-
-
-
-
150A
14
10
10
10
6
-
-
-
-
200A
10
10
10
10
5
-
-
-
-
300A
15
12
10
10
10
5
-
-
-
400A
13
10
10
10
10
5
5
-
-
500A
14
12
10
10
8
5
5
5
-
600A
14
12
12
10
10
7
5
5
-
100A
1
10
10
10
10
-
-
-
-
-
150A
-
-
-
-
5
-
-
-
-
300A
-
-
-
-
-
-
5
-
-
75A, 80A, 100A
3
10
10
5
5
5
-
-
-
-
150A, 200A
-
-
-
-
-
5
-
-
-
300A
5A
0,2 S
7
5
5
5
4
4
-
-
-
400A
8
6
6
5
5
-
-
-
-
500A, 600A
5
5
5
5
5
5
-
-
-
75A, 80A
0,5 S
5
-
-
-
-
-
-
-
-
100A
5
5
3
3
-
-
-
-
-
150A
5
5
5
5
5
-
-
-
-
200A, 300A
7
5
5
5
5
3
-
-
-
400A
14
12
10
10
10
5
5
-
-
500A
15
15
10
10
10
10
-
-
 
600A
15
12
12
10
10
10
5
-
-
75A
0.5
4
-
-
-
-
-
-
-
-
80A
5
-
-
-
-
-
-
-
-
100A
5
5
3
3
5
-
-
-
-
150A
5
5
5
5
5
-
-
-
-
200A
10
10
10
10
5
3
-
-
-
300A
14
10
10
10
10
5
-
-
-
400A
14
12
10
10
10
5
5
-
-
500A
15
15
10
10
10
10
5
5
-
600A
15
13
13
10
10
10
5
5
5
75A
1
3
3
-
-
-
-
-
-
-
80A
5
5
5
-
-
-
-
-
-
150A
12
9
8
7
5
-
-
-
-
300A
-
-
-
-
-
5
-
-
-
80A, 100A
3
-
-
-
5
5
-
-
-
-
150A, 200A
-
-
-
-
-
5
-
-
-
75A
5
-
-
-
-
-
5
-
-
-
 
Calculated values ​​of the DC resistance of the windings for instrument transformer current TSHP-0,66-I are given in Table 4
 
Table 4 Calculated values ​​of winding resistance to direct current for the device current transformer TSHP-0,66-I
 
Rated primary current
Secondary resistance (ohms) to direct current at the rated secondary current
1A
5A
for accuracy classes
3
1
0.5
0,5 S
0,2 S
5
3
1
0.5
0,5 S
0,2 S
75A
0,14
0,20
0,20
0,20
-
0.014
-
-
-
-
-
80A
0,25
0,25
0,25
0,25
-
0.01
-
-
-
-
-
100A
0,33
0,33
0.27
0.27
-
-
0.019
-
0.027
0.024
-
150A
0,50
0,45
0,45
0,45
-
-
0.028
0.028
0.032
0.032
-
200A
1,10
1,10
1,10
0,62
-
-
-
-
0.040
0.040
0.040
300A
-
0,96
0,96
0.78, 1.64
0.78
-
-
0.046
0.046
0.074
0.074
400A
-
-
2.00
2.00
1.32.???
-
-
-
0.070
0.070
0,05
500A
-
-
2,6
2,6
2,6
-
-
-
0.090
0.090
-0,11
600A
-
-
3.1.
3.1.
3.1.
-
-
-
0.130
0.130
0.130
 
Note. * - At rated secondary load 5V · A ** - at rated secondary load 10V · A;
 
Dimensions of the device current transformer TSHP-0,66-I are shown in Figure 1;
 
Figure 1 Dimensions of the device current transformer TSHP-0,66-I
 
TSHP-0,66-I - Current transformer - Drawing.
 
Weight:
- No tires - 0.7 kg;
- Bus - 0.9 kg;
One-minute test voltage instrument transformer current TSHP-0,66-I frequency - 3 kV;
Transformers of accuracy class 0,2; 0,5; 0,2 S and 0,5 S used in accounting schemes customer calculations, accuracy class 1.0 - in schemes of measurement;
The main advantages of instrument current transformers TSHP-0,66-I are given below;
Currently transformers produced at full standard range of rated primary current, while keeping accuracy classes as 0.5 and 0.2, and 0,5 S and 0,2 S, which allows to use them widely in computer-aided control and metering AMR ;
CT devices TSHP-0,66-I have several degrees of protection from unauthorized access:
- Transparent protective cover for sealing, protecting the secondary contacts, rating plate and the stamp, and ensures the safety of operation.
- Protective sticker that when trying to parse the transformer is broken, leaving visible signs of tampering;
The modern design and design tool CT TSHP-0,66-I allow the use of transformers with primary cable or bus and configuration of various sections, as well as install them in any position;
Availability of built-Cu coated with tin, it allows you to connect both copper and aluminum conductors;
Hazard CT TSHP-0,66-I provides a self-extinguishing plastic housing with high insulation class;
Shells themselves have three different colors - yellow, green and red, which is a common phase segregated marked;
Transformers are packaged in easy-to-consumer bottles, three pieces;
CT devices TSHP-0,66-I are absolute counterparts type transformers GPT-0 ,66-I;
Mount transformer by using the reference tabs or DIN-rail;
The new instrument current transformer TSHP-0,66-I has a convenient mounting potential output, which is in a sealable junction box;
The use of products of modern terminals can quickly be assembled secondary circuits;
 
The transformers are manufactured in model "U" or "T", are designed to operate under the following conditions:
Height above the sea level - no more than 1000 m.
Ambient temperature
- In operation - from -45 ° C to +50 ° C;
- Transport and storage - from -50 ° C to +50 ° C;
- Environment explosive, without dust, reactive gases and vapors in concentrations destroy metal and insulation;
- Working position - any;
Initial CT Bus device TSHP-0,66-I copper, tin-plated;
Warranty period - 8 years from the date of entry into operation of the transformer, but not more than 8.5 years from the date of shipment from the factory;
Service life CT TSHP-0,66-I - 30;
The unit is equipped with protective transparent cover for separate sealing of secondary findings;
Minimum permissible load current transformer unit TSHP-0,66-I for the windings of accuracy class 0,2 S and 0,5 S is 1B · A;
The certificate on the current transformers with secondary windings for accounting accuracy classes 0,2 S and 0,5 S indicates the measured current and the angular error at rated secondary burden 1B · A;
The manufacturer guarantees that the quality of the instrument current transformer TSHP-0,66-I to the technical requirements specifications provided the customer terms and conditions of storage, transportation, installation, operation, and its specified operational documentation.