SVKA 1-02.06-21 (CBKA 1-02.06-21)

available:
2 pieces
For order is possible effectively delivery of any quantity.

Processing units for apparatus SVKA 1-02.06-21 (CBKA 1-02.06-21; SVKA 1-02.06/21; SVKA1-02.06-21 SVKA1-02.06/21; cbka 1-02.06-21; cbka 1-02.06/21; cbka1-02.06-21; cbka1-02.06/21)

    Equipment for the control of the relative movements of SVKA 1-02.06-21 (CBKA 1-02.06-21) - products designed for continuous measurement and control of axial displacement.
    Controlled parameter - axial shift.
    Controlled value - static gap.
    Output Type - 0 - 5V.
    Frequency range - 0 - 1 Hz.
    Composition - No. CB2 + BS3-01.
    Overall dimensions:
    - DB2-04 - Ø5mm × 30mm;
    - DB2-05 - 8mm × 40mm;
    - DB2-08 - Ø 10 mm × 50 mm;
    - DB2-12 - Ø14, 5 mm × 70 mm;
    - DB2-026 - Ø30mm × 100mm;
    - Matching unit BS3-01 - 125 × 80 × 57mm.
    Weight:
    - Matching unit BS3-01 - 0.55 kg;
    - DB2-04 - 0.1 kg;
    - DB2-05; No. CB2-08 - 0.2 kg;
    - DB2-12 No. CB2-026 - 0.3 kg.
    Usually SVKA 1-02.06-21 (CBKA 1-02.06-21) used in the oil, gas, power and other industries.

    Structural features of SVKA 1-02.06-21 (CBKA 1-02.06-21)
 
    The equipment consists of SVKA 1-02.06-21 (CBKA 1-02.06-21) measuring channels with different functional purpose, the type and version. The structure of the channels SVKA 1-02.06-21 (CBKA 1-02.06-21) may include eddy current sensors with two embodiments of the sensor: the generator (DB) type for small     measurement ranges (up to 4 mm) or a transformer (DP) type for large measurement ranges (up to 60 mm).
    The principle of operation of equipment SVKA 1-02.06-21 (CBKA 1-02.06-21) based on conversion of eddy current sensors controlled the gap to an electrical signal and its further processing.

    Specifications SVKA 1-02.06-21 (CBKA 1-02.06-21)
 
    Measuring range of SVKA 1-02.06-21 (CBKA 1-02.06-21) and the maximum permissible error filed in Table 1.

    Table 1.
Type of sensors
DB2-04
DB2-05
DB2-08
Measuring ranges
± 0,25
± 0,5
± 1
Maximum permissible absolute error
± 0,01
± 0,02
± 0,03
Maximum permissible absolute error over the full operating temperature range
± 0,02
± 0,04
± 0,06
Type of sensors
DB2-08
DB2-12
DB2-26
Measuring ranges
± 1,5
± 2
± 5
Maximum permissible absolute error
± 0,05
± 0,07
± 0,15
Maximum permissible absolute error over the full operating temperature range
± 0,08
± 0,1
± 0,2

    The error alarm SVKA 1-02.06-21 (CBKA 1-02.06-21) of ± 0,2%. A noise level of the measurement range of ± 0,15%.
    Rated transformation ratio of eddy current sensors SVKA 1-02.06-21 (CBKA 1-02.06-21) has the following values:
    - DB2-04 - 32mA/mm;
    - DB2-05 - 16mA/mm;
    - DB2-08 - 8mA/mm, 5.33 mA / mm;
    - DB2-12 - 4mA/mm;    
    - DB2-026 - 1.6 mA / mm.
    Frequency range of eddy current sensors with matching unit is 0-10kHz.
    Operating temperature range for the equipment SVKA 1-02.06-21 (CBKA 1-02.06-21) has the following values:
    - Sensors - from -40 ᵒ C to +200 ᵒ C;
    - Matching unit - from -50 ᵒ ᵒ C to 65 C;
    - Secondary unit - from -40 ᵒ C and 65 ᵒ C.

Photos: SVKA 1-02.06-21 (CBKA 1-02.06-21)

SVKA 1-02.06-21 (CBKA 1-02.06-21) device image.
SVKA 1-02.06-21 (CBKA 1-02.06-21) device image.
SVKA 1-02.06-21 (CBKA 1-02.06-21) delivery set.
SVKA 1-02.06-21 (CBKA 1-02.06-21) delivery set.
SVKA 1-02.06-21 (CBKA 1-02.06-21) accessories and spare parts.
SVKA 1-02.06-21 (CBKA 1-02.06-21) accessories and spare parts.
SVKA 1-02.06-21 (CBKA 1-02.06-21) front view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) front view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) side view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) side view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) rear view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) rear view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) bottom view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) bottom view.
SVKA 1-02.06-21 (CBKA 1-02.06-21) drawing.
SVKA 1-02.06-21 (CBKA 1-02.06-21) drawing.