Electrical measuring instruments >> analog panel meters >> shunts >> shunts 75SHSMOM3

Shunt 75SHSMOM3

432 RUB
83 UAH
available:
255 pieces

Online prices include VAT.

For order is possible effectively delivery of any quantity.
Shunt measuring steady 75SHSMOM3 (75SHSM-OM3, 75SHSM OM3)
 
Shunt measuring steady 75SHSMOM3 intended to limit the extension measuring DC ammeters and counters Cove ampere-hours.
 
Product Specifications stationary measuring shunts 75SHSMOM3:
 
Accuracy class 0.5;
The voltage drop across the terminals of the potential for all grafts at rated current is 75mV;
Rated currents and nominal resistance of the shunt measuring stationary products 75SHSMOM3 summarized in Table 1;
Limits of error of shunt - ± 0,5%;
 
Table 1 The nominal current and nominal resistance of the shunt measuring stationary products 75SHSMOM3
Rated current
Intentional impedance
75A
1000 mkOm
100A
750 mkOm
150 A
500 mkOm
200A
375 mkOm
300A
250 mkOm
500A
150 mkOm
750A
100 mkOm
1000 A
75 mkOm
1500 A
50 mkOm
2000A
37.5 mkOm
3000A
25 mkOm
4000A
18.75 mkOm
5000A
15 mkOm
6000A
12.50 mkOm
7500A
10 mkOm
 
Maximum permissible variation of the resistance values ​​of the shunt products 75SHSMOM3 measuring stationary, appearing as a result of termoelektrodvi zhuschey power at nominal load current is equal to half the absolute value of the limit of permissible basic error STI shunt;
Maximum permissible variations in the values ​​of shunt resistance, which has two or more current clips on each side, resulting from the unequal distribution of power in the place of summing up the current to shunt off with one Toko vomu clamp on each side of the shunt is equal to half the absolute value of the limit of permissible basic error;
Shunt 75SHSMOM3 measuring steady-state is designed to operate at approximately rounding the air from -40 º C to +50 ° C and a relative humidity of 95% (at 40 ° C);
Shunts, intended for export to areas with cold-temperate and tropical climates, supplying lyayutsya for operation at temperatures from -40 º C to +50 ° C and a relative humidity of 90% (at 35 ° C) and the IME and the UT designation 75SHSMM3 75SHSMT2;
Overall dimensions and weight of products 75SHSMOM3 shunt measuring the stationary (non-current and potential terminals), we reduce the HN in Table 2;
The average lifetime of shunts to the cancellation - at least 15 years of age;
 
Table 2. Overall dimensions and weight of items measuring shunt 75SHSMOM3 stationary (non-current and potential terminals)
Measurement limit
Weight, kg
Overall dimensions, mm
75A
0.19
120h22h12
100A
0.25
130h30h12
150 A
0.29
130h22h12
200A
0.38
130h30h12
300A
0.54
130h30h18
500A
0.41
150h35h20
750A
0.6
150h50h20
1000 A
0.8
170h50h30
1500 A
1.05
170h50h50
2000A
3.5
200h80h50
3000A
4.4
200h105h50
4000A
7
240h145h70
5000A
11
240h160h70
6000A
11
240h160h70
7500A
13
240h210h70
 

Photos: Shunt 75SHSMOM3

75SHSMOM3 5000A shunt image.
75SHSMOM3 5000A shunt image.
75SHSMOM3 5000A front view.
75SHSMOM3 5000A front view.
75SHSMOM3 5000A side view.
75SHSMOM3 5000A side view.
75SHSMOM3 5000A overhead view.
75SHSMOM3 5000A overhead view.
75SHSMOM3 5000A bottom view.
75SHSMOM3 5000A bottom view.
75SHSMOM3 75A shunt image.
75SHSMOM3 75A shunt image.
75SHSMOM3 100A shunt image.
75SHSMOM3 100A shunt image.
75SHSMOM3 150A shunt image.
75SHSMOM3 150A shunt image.
75SHSMOM3 200A shunt image.
75SHSMOM3 200A shunt image.
75SHSMOM3 300A shunt image.
75SHSMOM3 300A shunt image.
75SHSMOM3 750A shunt image.
75SHSMOM3 750A shunt image.


Яндекс цитирования