Electrical measuring instruments >> digital panel meters

SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120 Digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120.

SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120

8 833 RUB
2 412 UAH

Online prices include VAT.

For order is possible effectively delivery of any quantity.
Digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120
 
Digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120 designed to measure current or voltage in AC circuits.
 
Technical characteristics of the instrument panel meters digital AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120:
 
Digital panel meters AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120 can be used in energy and other industries to control the electrical parameters.Devices digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120 are odnopredelnymi and have designs on the design, measurement range, the number of decimal places, the supply voltage, the presence of the interface, color indicators, accuracy class.
 
Type
Dimensions / cutout in the panel, mm
The height of the sign, mm
SCHP02M
96h48h145mm/90h42mm
14mm
SCHP02.01
96h48h90mm/90h42mm
14mm
SCHP72
72h72h100mm/68h68mm
14mm
SCHP96
96h96h100mm/92h92mm
20mm
SCHP120
120h120h100mm/112h112mm
20mm
Operating conditions
Operating Temperature Range ...... from +5 ° C to +50 ° C
Humidity of not more than ........... 80% at +25 º C
 
Technical specifications
The number of digital displays
4
Class of accuracy
0.5 or 1.0
Degree of protection front
IP40
Conversion time, not more
1.0 with
Galvanic isolation of input circuits
is
Electrical isolation of Nutrition
is
The presence of interface RS485 (for devices SCHP02M, SCHP96, SCHP120)
is
The rate of exchange of information via interface RS485, baud
4800, 9600, 19200, 38400
Maximum allowable overload of the input signal (duration)
150% (1 minute)
Frequency range of the measured signals:
 
Working documentation.
- Normal
from 40Hz to 1000Hz
45Hz to 65Hz from
Input impedance for voltage measurement, at least
1 M
The voltage drop across the device for measuring current:
for ranges 2mA, 20mA, 200mA, 1000mA, 2000mA, 1A, 2A.
for ranges 10mA, 100mA, 500mA.
for measuring ranges 5mA, 50mA
for ranges 5A
 
200mV
100mV
50mV
no more than 30mV
 
Type of scale devices digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120
Status indicators
(By jumpers on the rear panel)
"%"
H=48 km
Ordered (scale range corresponds to the order)
OFF
OFF
Time (scale range from 0 to 9999. *)
ON
ON
Interest (scale range ± 100.0 *)
ON
OFF
Line (scale range corresponds to a range of input signal)
OFF
ON
* - Matches the position of the point.
 
Wiring device digital panel meter AC SCHP02M, SCHP02, SCHP72, SCHP96, SCHP120 by the screw.The cross section of wires that are connected directly to the terminals, not more than 1.5 mm 2 for the devices SCHP02.01 and not more than 2.0 mm 2 for the devices SCHP02M, SCHP72, SCHP96, SCHP120.
 
Example of ordering
SCHP02M device, measuring range, 200A, rated secondary current of the external current transformer 5A, voltage 24 V DC with the possibility of redundancy, interface RS485, red indicators, accuracy class 0.5
SCHP02M-200A/5A-4 ,0-24VN-RS-0.5 K-TU 25-7504.198-2007
SCHP120 device, measuring range from 500V direct connection, supply voltage 85 to 242V AC or 100 to 265V DC, the interface is RS485, red indicators, accuracy class 1.0
SCHP120-500B-4 ,0-220VU-RS-K-1, 0, N 25-7504.198-2007
SCHP120 device with characteristics similar to the previous one, intended for use in a moderately cold climate with temperatures between minus 40 ° C to +55 ° C
SCHP120-500B-4 ,0-220VU-RS-K-1 ,0-UHL3 .1 W 25-7504.198-2007
SCHP72 device, measuring range from 5A direct connection, 5V DC regulated, red indicators, accuracy class 0.5
SCHP72-5A-4 ,0-5V-R-0.5 TU 25-7504.198-2007


Яндекс цитирования