Megger ELECTRON-1 (ELECTRON1, ELECTRON 1)
 
Megger ELECTRON-1 is designed for continuous automatic monitoring of insulation resistance of ship electric networks single-phase and three-phase AC voltage up to 400V, 50Hz-500Hz with ungrounded as presence detection in a controlled network, and in its absence.
 
Technical characteristics of the devices testers ELECTRON-1:
 
The device works fine under the following conditions:
- High level of humidity - 100% at temperatures up to +50 ° C;
- Changing the ambient pressure in the range 84kPa-212 8kPa;
- Ship's pitching to 45 º with period 16c and long slopes to 15 °;
- Operating temperature - 0 ° C to +50 ° C;
- Keeps working after being in extreme temperatures - 50 ° C and +65 ° C;
Note May be short-term work for 2 hours at a temperature of +60 ° C, and the error is not standardized;
Electronic equipment provides continuous automatic control of the insulation, allows visual observation of the numerical value of the insulation resistance from 0 m to 1 MW automatically includes audible and visual alarm when insulation resistance is below the specified set point;
Electronic equipment is powered from the ship's AC, 50 Hz ± 2,5 Hz voltage of 127V or 220V;
Voltage tolerance megger instrument ELECTRON-1 allowed the nominal -10% to +6%;
Power can be obtained both from the monitored network or from an external source;
In the latter case, the designer of the vessel in the supply unit must be provided for the possibility of removing the switch operating voltage-controlled network (meter megger ELECTRON-1, Operating supplies voltage to a controlled area network);
Main power when the light is activated and Chime is not PAINFUL 10W;
Measurement error does not exceed 5%, the error signal - 10% of the set point;
Megger instrument electron-1 has the following 5 settings - 0.5, 0.2, 0.1, 0.05, 0.25;
As sound warning device with megger ELECTRON-1 can be used to call or bell own power supplied via relay device;
Contact Options power beeper device megger ELECTRON-1:
- DC:
- 30V - 2A;
- Up to 250 V - 0.3 A;
- AC:
- Up to 250 V - 0.3 A;
Call bell or the apparatus megger ELECTRON-1 is not included;
Parallel connection of the device to any device which is its own source of DC voltage, are necessary;
Insulation resistance of electrical circuits megger instrument electron-1 on the walls must be less than:
- 20 M - under normal weather conditions - temperature +25 º C ± 10 ° C, relative humidity of 65% ± 15%, ± 100 kPa pressure 4kPa;
- 5 MOhm - at a temperature of +50 ° C ± 2 º C, humidity of 65% ± 3%;
- 1 M - at +25 º C ± 2 ° C, humidity of 95% ± 3%;
Dielectric strength relative to the body to check the voltage of 1.5 kV AC, 50 Hz;
Overall dimensions megger ELECTRON-1 - 175x195x224mm;
Weight - not more than 4.2 kg;
The manufacturer guarantees that the quality of the instrument megger ELECTRON-1 technical requirements specifications provided the customer terms and conditions of storage, transportation, installation, operation, and its specified operational documentation.